Rinnai Heating Specication Guide 02-13 | 23
Multiple heater positioning for total area heating
Heaters can be positioned side by side or facing each other as long as the following distances are
maintained. The table below shows approximate positioning for total area heating
WMA/WEA 16 WMA/WEA 24 WMA/WEA 40
A. Facing each other 8.0 m 9.8 m 15.0 m
B. Side by side 6.1 m 7.3 m 9.0 m
A
B
Indoor Super Ray WITH a heat shield
A
B
C
WMA/WEA 16 WMA/WEA 24 WMA/WEA 40
A Approximate height from floor to bottom
of burner (Rinnai recommend)
2.5 m 2.7 m 3.4 m
B Side clearance from mounting bracket 1.0 m 1.0 m 1.0 m
C Ceiling clearance from top of mounting
bracket
0.5 m 0.5 m 0.6 m
With a heat shield fitted heat is deflected
down and out so the side clearance
needs to increase from 0.5 m to 1 m.