PARA
Description
Range / Explanation
Factory
Setting
User
Access
6
Inrush
optimization
OFF
Not active
OFF Yes
1-8
hours
The
amount of time the boiler will allow itself to
operate before a heating event begins in order to
be at the desired temperature of that event.
NOTE: This value is the allowed time to
operate
the boiler may not use the entire value
8
Room frost
protection
OFF
Not active
50°F No
41-
86°F
If in vacation or economy/absent mode, or if
ECO is selected at PARA 1, the boiler will fire if
this temp is detected by the RS100 (in the room).
NOTE
: If the RS100 is set for outdoor reset mode (PARA 3=OFF or 1, PARA 4=OFF), a modem-driven
switch can be placed in parallel with the outdoor sensor. When this switch closes, the RS100 will use
this parameter to engage freeze protection. This allows a user to remotely preheat a second home.
Unmixed (HC) Circuit Parameters (continued)
9
Exceeding
room temp
control
OFF
Not Active
Off No
33-41
This
setting will turn off the boiler if it senses the preset overshoot. The
boiler will restart at the set point minus
-1°F.
NOTE: The conversion to
Fahrenheit is incorrect. Use this key: 33=1
°F overshoot, 34=2°F
…41=9
°F;
NOTE: This parameter is ignored if Para 3=OFF or 3 or Para 4=OFF