Rinnai Australia 10 Operation / Installation Manual
If flue length exceeds 1.5 metres, dip-switch 1 of SW1 located inside the HD unit is to be switched to
the ‘OFF’ position.
For all further information on Internal Flueing, please refer to separate Flueing manual supplied with
Flueing components.
Multiple Flue Terminals
Dimension 'H' in AS/NZS 5601 Figure 6.2 does not apply when multiple Rinnai external water heaters
of the same model are installed on the same vertical face with flue terminals at the same height. Under
these conditions appliances can abut each other as shown below:
The terminal clearances stated in AS/NZS 5601 do not apply to the INFINITY HD200 and 26 litre
internal water heaters when they are installed side by side. AGA certification allows for a minimum
horizontal separation of 160 mm for roof terminals and 270 mm for wall terminals.
Only Rinnai Flueing systems can be used with Internal Water Heaters. Non-Rinnai
Flueing systems are not certified and will not be covered under warranty.
NOTE
UP UP UP
FFROOFCOWL
FFWPLATE
350
160
225
270
Minimum clearance 500
FFWALLTERM
FFPIPE1000
FFCPIPE